BİR EŞANJÖR BORUSUNDA DELİKLİ TÜRBÜLATÖRLERİN ISI TAŞINIM KATSAYISI VE BASINÇ DÜŞÜŞÜ ÜZERİNDEKİ ETKİLERİNİN SAYISAL OLARAK İNCELENMESİ


Fırat İ.

7. Uluslararası Bilimsel Araştırmalar ve İnovasyon Kongresi , Ankara, Turkey, 16 - 17 December 2023, pp.377-387

  • Publication Type: Conference Paper / Full Text
  • City: Ankara
  • Country: Turkey
  • Page Numbers: pp.377-387
  • Erzincan Binali Yildirim University Affiliated: Yes

Abstract

In this study, the effects of prism turbulators with different numbers of holes were examined with the Ansys-Fluent 2021 program to increase the heat transfer coefficient and reduce the pressure drop in a heat exchanger pipe. The distance between the perforated prism turbulators increasing from the test pipe entrance to the exit is 160 mm. Analyzes were carried out in the range of Re=11871-19110. Findings have shown that perforated prism turbulators offer notable benefits compared to plain pipe. For the increasing Re number due to the increase in fluid flow rate, both heat transfer coefficient values and pressure drop values increased. The maximum pressure increase rate compared to the empty pipe was 1421.74% in the 6-hole prism turbulators at Re = 19110. The maximum heat transfer coefficient increase rate compared to the plain pipe was 55.55% in the 6-hole prism turbulator at Re = 11871. Although 6 perforated prism turbulators are more advantageous in terms of heat transfer coefficient increase, it has been concluded that 1 perforated prism turbulator is more advantageous in terms of pressure drop.